Product Types

Highlight

Screened Alarm Cable

Screened Alarm Cable
Alarm Cable, TCCA conductor, PVC Insulation, Overall Screened, PVC Jacket, Type 3
icon Datasheet Download

Application

Primarily used in security, alarm, instrumentation, communication, surveillance, and monitoring systems

 

General

Conductor Tinned Copper Clad Aluminium
Insulation Material  PVC
Number of Cores 4 to 12
Insulation Colour See Table 1
Wrapping PET Film
Drain Wire Tinned Copper Clad Aluminium
Screening AL/P Foil
Rip Cord Yellow Nylon
Jacket Material PVC
Jacket Colour White

 

Dimensions

Conductor Diameter 7/0.20 mm
Insulation Diameter 1.05 mm
Insulation Thickness 0.25 mm
Drain Wire Diameter 7/0.20 mm
Diameter over Jacket See Table 2

 

Electrical Characteristics

Rated Voltage 30 V
Conductor DC Resistance 155 Ohms/km Max.
Insulation Resistance  200 MOhms/km Min.
Test Voltage 500 V for 1 Minutes

 

Mechanical Characteristics

Operating Temperature -20℃ to +60℃
Bend Radius (Stationary | Installation) 5 x OD mm | 10 x OD mm
UV Resistance  ISO4892-3 (500 Hours) 

 

Standard and Compliance 

RoHS 3 (EU 2015/863)  Compliant
REACH  Compliant
Manufactured in accordance to BS 4737 Type 3
Warranty 3 Years (Indoor)  

 

Table 1. Core Colours

No. of Cores

Identification Colours

4

Red, Blue, Green, Yellow

6

Red, Blue, Green, Yellow, White, Black

8

Red, Blue, Green, Yellow, White, Black, Brown, Violet

10

Red, Blue, Green, Yellow, White, Black, Brown, Violet, Orange, Pink

12

Red, Blue, Green, Yellow, White, Black, Brown, Violet, Orange, Pink, Turquoise, Grey


Table 2. Variants         

Part No.

No. of Cores x Cross-sec.

[mm2]

Outer Diameter

[mm]

Copper Index

[kg/km]

Weight

[kg/km]

OS4C-22-LW-TY3

4 x 0.22

3.80

N/A

23.4

OS6C-22-LW- TY3

6 x 0.22

4.30

N/A

30.6

OS8C-22-LW- TY3

8 x 0.22

4.80

N/A

37.2

OS10C-22-LW- TY3

10 x 0.22

5.20

N/A

44.6

OS12C-22-LW- TY3

12 x 0.22

5.40

N/A

51.2