Product Types

Highlight

OSP1-14-PV-GRY-Eca (8720)

OSP1-14-PV-GRY-Eca (8720)
1P 14 AWG Str TC, PE Ins, OS, 16 AWG Str TC Drain Wire, PVC Jkt CPR Eca
icon Datasheet Download

Application

Up to 600V analog signals ; up to 600V digital control ; line level audio; voice communications; panel wiring

 

General

Inner Conductor 14AWG Stranded tinned copper
Insulation  PE
Pairs 1
Insulation Colour Black(RAL 9011), Clear
Overall Shiel AL/PET
Drain Wire 16AWG Stranded Tinner Copper
Jacket Colour Grey (RAL7042)
Outer Jacket PVC

 

Dimensions-(mm)

Conductor Diameter 19x0.361
Insulation Diameter 3.55
Nom. Thickness 0.87
Drain Wire 19x0.29
Diameter 9.0
Nom. Thickness 0.9

 

Electrical Characteristics

Rated Voltage 450/750V
Max. Recommended Current [A] 9.5 Amps per conductor @ 25℃
Nominal Conductor DCR 10 Ohm/Km @20℃ Max
Nominal Outer Shield DCR 16 Ohm/Km @20℃ Max
Impedance Specification 70±10 Ω
Insulation Resistance 200MΩ·km
Core to Core Capacitance
75±20 pF/m Max
Core to Shield Capacitance 150±25 pF/m Max
Rated Temperature -30℃ + 70℃
UV resistance ISO 4892-3

 

Standard and Compliance 

CPR Classification Eca
RoHS 3 (EU 2015/863) Compliant
REACH Compliant
Flammability EN 60332-1-2