Product Types

Highlight

LI2Y(St)CY

LI2Y(St)CY
Control Cable, Stranded Bare Copper Conductor, PE Insulation, Pes Tape, Al-Pes Tape, Tinned Copper Braid, PVC Jacket
icon Datasheet Download

Application

  • In places where electro-magnetic interference and influence exists
  • Instrumentation and Control Engineering
  • Industrial Electronics
  • Computers and Office Machines
  • Indoor Communication Systems
  • Indoor Sound Systems
  • Security Systems

 

General

Conductor IEC 60228; DIN VDE 0295; EN 60228 Class 5
  Stranded Electrolytic Bare Copper
Insulation EN 50290-2-23 PE Compound
Colour Code DIN 47100
Stranding In layers of optimum pitch
Wrapping Pes Tape
Screen Al-Pes Tape + Tinned Copper Braid
Sheath EN 50290-2-22 PVC Compound
Sheath Colour RAL 7001 Grey

 

Electrical Characteristics

Insulation Resistance 5000MΩkm
Working Voltage 0,22 ve 0,34 mm² = 250 V
  ≥ 0,50 mm² = 300/500 V
Test Voltage (AC) 0,22 ve 0,34 mm² = 1200 V
  ≥ 0,50 mm² = 2000 V

 

Mechanical Characteristics

Operating Temperature -30℃ to +70℃
Bend Radius 10 x OD mm

 

Standard and Compliance

CPR Classification Eca
Flammability IEC 60332-1-2
RoHS 3 (EU 2015/863) Compliant
REACH Compliant
Warranty 3 Years (Indoor)

 

Variants

Conductor Resistance

Operating Voltage

Effective Capacitance

Inductance

Current Carrying Capacity

mm2

Ω/km

300V/500V

70pF/m

Mh/km

0.67

A

0.22

79

2.5

0. 34

56

4.5

0.50

39

6.0

0. 75

26

13

1.0

19.5

16

1.5

13.3

20

2.5

7.98

25

*All dimensions in 100, 200 or 500 m length on drum.