OFBP2-24-PH-GRY-B2ca (9842)
2 P #24 Str TC, PE Ins, OS+TC Braid, LSZH Jkt, CPR B2ca s1a,d0,a1
Datasheet Download
Application
RS-485, POS; Computer communications; Low Voltage Analog Signals (4-20ma, 0-10v, ...); Low Voltage Digital Control (24v, …); Line Level Audio; Panel Wiring; serial communication (RS-485 standard) comprising of PLCs, VFDs, HMIs, motors, RTU, SCADA, etc. within noisy environments over long distance, etc.
General
| Inner Conductor | 24AWG Stranded Tinned Copper |
| Insulation | PE |
| Pairs | 2 |
| Insulation Colour-1 | White/Blue Stripe, Blue/White Stripe |
| Insulation Colour-2 | Orange/White Strip & White/Orange Strip |
| Colour | Blue(RAL 5015 );White(RAL9003) |
| Orange(RAL2008) | |
| Foil | AL/PET |
| Drain Wire | 24 AWG Stranded Tinned Copper |
| Braiding | Tinned Copper Braiding 90% coverage |
| Rip Cord | Yes (White) |
| Jacket Colour | Grey (RAL7001) |
| Outer Jacket | LSZH |
Dimensions-(mm)
| Conductor diameter | 7x0.20 |
|
Insulation Diameter
|
1.75 |
| Nom. Thickness | 0.57 |
| Drain Wire | 7x0.20 |
| Braiding Construction | 24x7/0.11 |
| Diameter | 7.6±0.9 |
| Nom. Thickness | 1.1 |
Electrical Characteristic
| Rated Voltage | 450/750V |
| Max. Recommended Current [A] | 2.1 Amps per conductor @ 25℃ |
| Nominal Conductor DCR | 95 Ohm/Km @20℃ Max |
| Insulation Resistance | 200MΩ·km |
| Impedance Specification | 120±15 Ω |
| Rated Temperature | -30℃ +70℃ |
| UV resistance | ISO 4892-3 |
Standard and Compliance
| CPR Classification | B2ca s1a,d0,a1 |
| RoHS 3 (EU 2015/863) | Compliant |
| REACH | Compliant |
| Flammability | EN 60332-1-2 |
| Smoke Density | EN 61034-2 |
| Halogen Acid Gas Test | IEC 60754-1 |
| Corrosive Gases Test | IEC 60754-2 |
| Reaction to Fire - Bundle Flame Test | EN 50399 |
| Warranty | 3 years (indoor) |